WELCOME , Guest !
Call Us Now At1-888-600-5426
UPSFEDEXFREE SHIPPING OVER $100 (Continental U.S.) Fast Quotes for International Shipments

How Much Chlorine To Inject? Treat Iron & Manganese Before Iron Filters

Chlorinator pump and alum injection pumpHow much chlorine to inject?  A common question we often get is, how much chlorine do I need to inject before my iron filter to treat iron, manganese and hydrogen sulfide (rotten egg odor)?

The short answer is:

  • 0.62 mg/l of chlorine per mg/l of iron;
  • 1.29 mg/l of chlorine per mg/l of manganese
  • 8.33 mg/l of chlorine per mg/l of sulfide

Note that mg/L (milligram per liter) is the same as saying PPM (parts per million).

Pre-Treatment With Chlorine and Filtration with Pro-OX Manganese Dioxide Media

A rapid and efficient method for removing iron and manganese and hydrogen sulfide is to chlorinate the raw water, allow 30 to 60 second retention time and filter with Pro-OX manganese dioxide filter media.

A level greater than 0.5 mg/l of oxidant (chlorine) should be injected into the storage tanks and distribution system to inhibit the growth of iron and sulfur bacteria.  

chlorine inject pro-ox iron filterWater is received from the well source and treated with chlorine to oxidize the iron, manganese, and sulfides present. Electromedia®  may be used with any number of oxidants. The iron is oxidized to ferric iron; the manganese to the manganic form, and sulfides are oxidized to sulfate.

Sulfate is common in water supplies and does not contribute objectionable taste or odor. A sufficient amount of chlorine is added to the water to meet the chemical demand and reach the chlorine breakpoint. A minimum free chlorine residual of 0.5 mg/l is provided to the distribution system. A higher residual may be injected depending on conditions.

How Much Chlorine To Inject?

Stoichiometry is used to determine the amount of reactants (in this case chlorine) that are needed in a given reaction. Describing the quantitative relationships among substances as they participate in chemical reactions is known as reaction stoichiometry.

The stoichiometric equivalent for chlorine needed to oxidize iron, manganese, and sulfide is:

  • 0.62 mg/l of chlorine per mg/l of iron;
  • 1.29 mg/l of chlorine per mg/l of manganese
  • 8.33 mg/l of chlorine per mg/l of sulfide
  • Plus organic demands which may be present, determined by jar testing or field pilot tests.

Note that even though hydrogen peroxide can be used, it does not work well if manganese is present.  For iron with manganese, chlorination or ozone works best.